A low temperature self-regulating heat tracing cable. Ideal for
freeze protection or process temperature maintenance BSX cables
are approved for use in ordinary (nonclassified) areas and
hazardous (classified) areas. With braiding only for added
safety.
Operating Voltage: 110-120 or 208-277 VAC.
Maximum operating temperature: 65°C
A low temperature self-regulating heat tracing cable. Ideal for
freeze protection or process temperature maintenance RSX 15-2
self-regulating heating cable is designed for applications where
the watt density requirements preclude the use of the standard
range of BSX cables. With braiding only for added safety.
Operating Voltage: 208-240 VAC.
Maximum operating
temperature: 65°C
Thermon KSX 10-2 heat tracing cable is self-regulating and
capable of being maintaining temperatures up to 121ºC and is
ATEX and IECEx certified allowing it to be used within
potentially explosive atmospheres.
Maximum Circuit Length
117m.
Maximum operating temperature: 121°C.
A high temperature self-regulating heat tracing cable. Ideal for
freeze protection or process temperature maintenance where high
temperature exposure capability is required HTSX withstands the
temperature exposures associated with steam purging.
Operating Voltage: 110-120 or 208-277 VAC.
Maximum
operating temperature: 150°C
A low temperature self-regulating heat tracing cable. Ideal for
freeze protection for a variety of refrigeration and freezer
applications. FLX cables can be cut to length and are available
in 3 power outputs: 5-FLX-2: 16 10-FLX-2: 33 " and 15-FLX-2: 49
watts per meter [power output at 10°C] With braiding only for
added safety.
Operating Voltage: 240 VAC.
Maximum
operating temperature: 65°C
A high temperature constant wattage heat tracing cable. Ideal
for freeze protection or process temperature maintenance This
cable is used in rugged environments, typically in refineries.
Operating Voltage: 110-120 or 208-277 VAC.
Maximum
operating temperature: 215°C
A low temperature parallel resistance constant watt heat tracing cable Designed to provide frost heave protection of cryogenic storage vessels Cut-to-length parallel circuitry for field fabrication Fibreglass overlay Nominal watt density: 16-33 W/m Maximum Operating Voltage: 690 VAC
TEK & HTEK series resistance constant Watt heating cables are
used where circuit lengths exceed the limitations of parallel
resistance heating cables. TEK & HTEK withstands the temperature
exposures associated with steam purging.
Operating
Voltage: 600 VAC.
Maximum Exposure Temperature: 260°C
Mineral Insulated Cable is known as the most durable cable in
the world. It is the ideal choice when an application's
temperature and power output requirements exceed the
capabilities of self-regulating and constant wattage cables.
Operating voltage: 750 VAC.
Maximum Exposure
Temperature: 500 ℃.